Hi all. I have another questions. [snip] 2) Parameter P219. We use a braking resistor.Do you need to specify the power of the resistor in the parameter? 3) Colleagues advise me to switch to vector control of the drive.How do you think? Should I start working on this? I also wanted to write - that I am a beginner.in work with frequency converters ...Тhank you for your responses! ------------------------------------------------------------------------------------------ |
Last edited by: Alex A223 at: 12/28/2021 09:43:15Last edited by: Jen_Moderator at: 12/28/2021 09:55:08New subject after splitting. Division of question into separate topics. |
|
12/28/2021 9:53 AM | |
Joined: 6/19/2017 Last visit: 9/6/2024 Posts: 8175 Rating: (172) |
New question published by Alex A223 is split to a separate thread with the subject Identification of motor parameters in a stationary mode . Best regards |
12/28/2021 11:41 AM | |
Joined: 3/27/2008 Last visit: 10/9/2024 Posts: 1140 Rating: (142)
|
2) P219, Sets the braking power of the connected braking resistor. 3) V/F control is a simple motor control, changing to V/F is a good method of diagnosis. Set P1300 = 0, for V/F control. Tractor |