Import of a Technical Question of the User NuTriStAr
|
12/16/2014 11:26 AM | |
Joined: 1/28/2009 Last visit: 9/10/2024 Posts: 6849 Rating: (1365)
|
Hello, Modules on bothh racks should have same order number and version.In case of any mismatch, your H-Set up never enters the redundant mode.I don't think your idea works for an H redundant system.
Best regards, Hamid Hosseini |
Last edited by: hdhosseini at: 12/16/2014 12:38 PM |
|