Joined: 12/4/2020 Last visit: 2/25/2023 Posts: 7 Rating: (0) |
Thanks a lot. I will try it |
2/5/2021 10:06 AM | |
Joined: 12/4/2020 Last visit: 2/25/2023 Posts: 7 Rating: (0) |
It's made on one PC with adressess 192.168.1.39 for VTS, 192.168.1.230 for XWorks Simulator |
2/5/2021 3:02 PM | |
Joined: 1/2/2012 Last visit: 4/24/2024 Posts: 27 Rating: (7) |
I was strugeling with the same isue 2 years ago. Albis helped me in this thread. https://support.industry.siemens.com/tf/nl/nl/posts/simulation-pxc50-100-200-in-combination-with-desigo-cc-v3-0/184259/?page=0&pageSize=10 He gave me the instructions in this attachement. Hope this helps you. Other wise contact your local support. p.s. Don't use port 47808 but use hex A000 or decimal 40960 in ALL your applications. AttachmentXWPControllerSimulation_DesigoCC_Connection_en.pdf (374 Downloads) |
This contribution was helpful to1 thankful Users |