5/12/2011 10:38 AM | |
Joined: 7/2/2008 Last visit: 8/26/2024 Posts: 928 Rating: (308)
|
Hello Victor Yeo, I hope my answer is not too late to be helpful. please use IW50 instead of PIW50. It will work this way. The redundant I/O blocks compare PIW50 to PIW100 and save the accepted result in IW50. So, in your program you must always depend on the process image not on the peripherals themselves. To understand more about the difference between IW and PIW, check Where and when do you need peripheral addressing? Best regards. H-H |
This contribution was helpful to1 thankful Users |