6/12/2018 6:39 AM | |
Joined: 4/28/2015 Last visit: 6/29/2021 Posts: 4 Rating: (1) |
Siemens provided HSP 0244 HSP 0244 can be installed in PCS7 V8.2 But can not be installed in PCS7 V9.0 |
6/13/2018 10:39 AM | |
Joined: 4/28/2015 Last visit: 6/29/2021 Posts: 4 Rating: (1) |
Nobody meet this issue? PN/PN coupler is not applicable for PCS7 v9.0 redundancy System? |
7/12/2018 7:16 PM | |
Posts: 3 Rating: (0) |
This solution is become available with SP1 (Service Pack 1) of PCS 7 V9.0. |