Can I archive any process value less 500 ms in WINCC Explorer 7.0. I want to take or record four process readings in one sec. Please let me know is there any limiting range (i.e. 500 msec) as WINCC explorer tag logging does not show options less 500 msec . I want to configure it for 250 msec. How it could be possible ? ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 06/26/2020 10:20:34New subject after splitting |
|
6/26/2020 11:39 AM | |
Joined: 5/16/2014 Last visit: 9/12/2022 Posts: 7298 Rating: (2164)
|
Hello ANUJ9891i, you can use the process-driven archiving of process values, https://support.industry.siemens.com/cs/ww/en/view/23629327 If you would not have a PLC with SFB37, you could use
Georg Berghof AttachmentTLGInsertArchivData.pdf (47 Downloads) |