Hello, since the SINAMICS S210 doesn't have DCC the winder application can't be realized in the SINAMICS S210. But there is an application example for the winder application in a S7-1500: https://support.industry.siemens.com/cs/ww/en/view/58565043 Also, the SINAMICS S210 isn't designed for SIMATIC S7-1200 CPUs. This combination may cause performance problems, especially at high performance application like for example a winder. There is an FAQ in SIOS for which controllers the SINAMICS S210 is designed: https://support.industry.siemens.com/cs/ww/en/view/109761460 Best Regards, Technical Support for SINAMICS S210 |