5/14/2021 8:19 PM | |
Joined: 9/20/2018 Last visit: 1/2/2024 Posts: 42 Rating: (4) |
I am Also facing this issue. We are doing multiuser engineering where We have multi project and project folder shared over network. .All PC's are in Domain. People having their Login user Id and own password. Sometimes what happens if 1 user open project in his machine while opening we are getting popup " Cannot start database " after clicking Ok multiple time this popup is coming and at the end multi project will open but user project and project library is missing . Sometimes it is also happen that after clicking ok on Popup user can see all user project , Charts , hierarchy as well . he can open chart and do editing . If the same user login into other PC then this popup is not showing. Can anyone explain why this popup is coming or in what cases this popup will come. Also my worry is after this popup should we continue working or not ? We have PCS7 SP3 . Thank you in advance.
------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 05/17/2021 09:23:56New subject after splitting |
|
5/15/2021 1:13 PM | |
Joined: 9/9/2015 Last visit: 4/11/2024 Posts: 727 Rating: (268) |
Hi, In domain network, the most critical configuration is user right. You have to ensure in your current computer management user group , the local user group is being mapped to either domain user group or domain user. For example, if you have a domain user group SiemensPCS7/SIMATIC HMI, then this domain user group must map to your local SIMATIC HMI user group. And then the domain user must map to the domain user group. Another method is the domain user must map to the local user group. |
Please give me 5 stars Rating if my post is helpful for you. :) |
|
This contribution was helpful to1 thankful Users |
Follow us on