6/28/2007 10:04 PM | |
Posts: 3149 Rating: (171)
|
Hi please attach your WinCC logfiles here... nemo |
7/10/2007 11:54 PM | |
Joined: 11/18/2006 Last visit: 10/8/2012 Posts: 3 Rating: (0) |
Hello Please read in the ZIP file the archive named comments with thelast test. And with the Log Files Thanks Jorge Camalich AttachmentSIMATIC_S5_ETHERNET_LAYER_4_50.zip (101 Downloads) |
7/11/2007 7:47 AM | |
Posts: 3149 Rating: (171)
|
Hi please attach ALL files, I guess there are some files missing.... nemo |
7/16/2007 9:54 PM | |
Posts: 8 Rating: (0) |
I am the final user for this case. I am attaching the other diagnostic files, as they are a lot, I will be attaching in 5 attachments. Thanks for your help. Chilamacj AttachmentSIMATIC_S5_ETHERNET_LAYER_4_07.zip (110 Downloads) |
7/16/2007 9:57 PM | |
Posts: 8 Rating: (0) |
Second attachment..... chilamacj AttachmentSIMATIC_S5_ETHERNET_LAYER_4_17.zip (77 Downloads) |
7/16/2007 9:59 PM | |
Posts: 8 Rating: (0) |
Third attachment.... chilamacj AttachmentSIMATIC_S5_ETHERNET_LAYER_4_35.zip (72 Downloads) |
7/16/2007 10:01 PM | |
Posts: 8 Rating: (0) |
Fourth attachment.... chilamacj AttachmentSIMATIC_S5_ETHERNET_LAYER_4_43.zip (89 Downloads) |
7/16/2007 10:04 PM | |
Posts: 8 Rating: (0) |
Fifth and final attachment.... chilamacj AttachmentWinCC_Sys_05.zip (87 Downloads) |
8/1/2007 8:42 PM | |
Posts: 8 Rating: (0) |
Just to inform the problem is solved, It was a firmware in the CP1430TF cards in the PLCs that does not show when you are using a CP1413 in the PC but when you change to a CP1613 it just happens. The correct firmware versions for the Cp1430TF cards in the PLCs you can checkit with the attached document extracted for Simatic net support. As an additional information, the problem occurs equally with the old CP1613 (A1) in the PC as with the new CP1613 (A2), and solves equally changing the firmware in the CP1430TF card in the PLCs. A lot of Thanks to Nemo and J_Bell for your support, this was one of these weird problems that without prior experience is very difficult to pinpoint. Regards, Juan A. Camalich Chilamac AttachmentCP1430 Firmware Upgrade v309.pdf (88 Downloads) |