Hi, unhapply I don't have any example about it, however you should 1 - Activate diagnose interrupts/functions on the devices 2 - Create and load a OB82 3 - In OB82 use the OB header information to get the information if you need 4 - If necessary, call diag blocks with the OB82 header information to obtain detailed informations. Take a look also in http://support.automation.siemens.com/BR/view/en/42781105 |