Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (872) |
Simatic Manager Step 7 does not support plc.arc files. |
1/5/2020 5:23 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (872) |
PLC.arc i.e. series start up file is created by HMI software & not by step 7. Its purpose is for back up only & it can be download/upload convinently by RS232 interface with PCIN software. Step 7 does not support it.
I guess OP30 is connected to 810D CCU via MPI, it means NCK communicates directly with OP on MPI, please check. I suggest you to please follow below steps & check. Select SERVICES ---> READ IN DATA ----> DATA -----> START , after pressing START key you can see target directory window where in two options will be displayed i.e. 1 - path/workp.archieve file & 2 - copy to clipboard. Select path/workp.archieve file option & press OK. Data transmission will take place & PLC.arc file will get transfered to appropriate directory. Please check & revert if any problem occurs. BTW is it same problem mentioned in this CCU1 810DE sw1.6/OP 030 How to Restore .ARC Files to CCU topic?
|