Hello everyone, I'm facing trouble while downloading program into S7-200 smart ST-60 hardware. Error "The indicated data page does not exist" I'm using MicroWin Smart V2.1. Attached screnshot of error. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 11/04/2020 11:02:12New subject after splitting |
|
11/10/2020 5:58 PM | |
Joined: 7/5/2017 Last visit: 1/12/2021 Posts: 164 Rating:
|
Hello Hardik, I give one tip for solving this problem. Take a fresh upload from PLC select only PRG block or subroutine, don't take upload with data block. Then modify as you want and download to PLC. This will help you so please rate it. Regards Rudra automation
|