9/5/2006 1:39 PM | |
Joined: 4/24/2006 Last visit: 4/25/2024 Posts: 8613 Rating: (1147) |
Hello sandoz, Have you seen the following faq: http://support.automation.siemens.com/WW/view/en/9260793 Par. 3.5.1 tells something about number of slaves. You don't have to buy a dongle, you order the right module. Hope this will help. Best regards, Wizard |
9/6/2006 9:47 AM | |
Joined: 4/24/2006 Last visit: 4/25/2024 Posts: 8613 Rating: (1147) |
Hi sandoz, When you use RS232, it will be a point to point communication. So this means just 1 slave! http://support.automation.siemens.com/WW/view/en/9127658 When you use RS485 it's a multidrop communication. Best regards, Wizard |