1/4/2008 9:21 PM | |
Joined: 1/7/2006 Last visit: 11/17/2023 Posts: 2705 Rating: (318)
|
Dear Benson, You may read out the SSL data of the diagnostic buffer. The SSL-list is in the handbook System Software for S7-300/400 System and Standard Functions to find under chapter 33.30. 33.30 SSL-ID W#16#xyA0 - Diagnostic Buffer
If you read the partial list SSL-ID W#16#xyA0, you obtain the entries in the diagnostic buffer of the module. |
I hope that the answer will help, if you have still questions, don't hesitate to ask me. |
|