Dear sir, How to change the r61001 parameter for communication to the intouch without any software. While changing from its BOP's key pad, it is showing the read only parameter. I have to set 192.168.0.1 for 4 index of r61001 parameter. Please reply. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 2/8/2018 7:50:53 AMNew subject after splitting |
|
2/9/2018 12:03 PM | |
Posts: 2 Rating: (0) |
I am using G120 siemens drive. |
2/9/2018 12:09 PM | |
Joined: 5/12/2006 Last visit: 9/24/2024 Posts: 22371 Rating: (3014) |
check parameter p8921 |