10/6/2006 10:23 AM | |
Posts: 8 Rating: (0) |
I want to communicate ControlLogix(AB) and S7-300 By Profibus But I don't know how to configure SST_PFB-CLX and cp315-2dp. how to configure them ? |
10/6/2006 11:02 AM | |
Joined: 4/24/2006 Last visit: 9/25/2024 Posts: 8742 Rating: (1168) |
Hello, You have to configure the CPU315-2DP as slave. Then you can configure the Inputs and Output area you want to communicate with master. Here are some links, showing how to configure CPU315-2DP as slave: http://support.automation.siemens.com/WW/view/en/19449428 http://support.automation.siemens.com/WW/view/en/6709721 With the master you have to use a GSD fileto useCPU315-2dp as a slave. Consider the communication area you have configured in Step7. They have to be identical, pay attention to the consistency. Hope this will help. Best regards, Wizard |