Posts: 5 Rating: (0) |
Hi Everyone, I would like to use the OS simulation, but it seem that all block are in grey (as in no connection to PLC). I am using PLCSIM to perform the simulation. All programs are downloaded. What could be wrong? Kindly advice.. Splitted from CEMAT Blocks in OS simulation ??. |
Last edited by: O_Moderator at: 3/28/2011 1:02 PMnew subject after splitting |
|
3/29/2011 7:05 PM | |
Posts: 2661 Rating: (279)
|
See section 4.2.2 in the following manual: SIMATIC Process Control System PCS 7 Compendium Part A - Configuration Guidelines . . . it is essential that the ES-AS connection has the same name as the OS-AS connection . . . Regards |