8/9/2011 3:07 PM | |
Posts: 3609 Rating: (29) |
here more detailed information
AttachmentImport Lizensen.zip (192 Downloads) |
8/10/2011 1:44 PM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
Dear Phantom75 I have removed the WinCC RC PO license and activate runtime and take the screenshot : A) Automation License Management ( attachment No.1 ) B) Quantity of process objects and License ( attachment NO.2 ) C) License Error ( attachment NO.3 ) D) Detail of license error ( attachment NO.4 ) E) After Press "Open" key ( attachment NO.5 ) >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> Also after prepare this 5 attachment, I have closed the RT ,WinCC explorer, and put back the license, But the problem didn't solved. Attention please ! After put back the license the Detail of License error and the screen after press "Open" key, have a little change. in compare with First question in top of this conferense( before remove the WinCC RC PO license): D) Detail of license error ( attachment NO.44 ) E) After Press "Open" key ( attachment NO.55 ) Best regards Thank you. AttachmentAttachment.zip (190 Downloads) |
8/15/2011 1:00 PM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
Dear Phantom75 Special thanks of your answers. According to your request, I have created a new project and Copy the old project on it. After that,i have OS compiled on the OS.then I openned the WinCC run time monitoring. In the beginning, it seems everything is ok. But when I add new tag logging for Digital Values, plus to Analog values tag logging, after saving the tag logging, simultaneously the RC PO License Errore appears. Please see the TagLogging & Error window ,in the attachment. AttachmentTAGLOGGING.zip (186 Downloads) |
Last edited by: SA_JOO at: 8/15/2011 1:02 PM |
|
8/21/2011 2:43 PM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
Dear April Hi, I have removed the RT Licenses from my PC, but after run the monitoring,My problem was still unresolved. After some checking, i found that :when the number of Archive Tags in Taglogging, exceed from 512, the licence error appears. else there is no license error. For more Information, see the attachments Please: a)The number of external WinCC tag and its limit in my project is:1618 of 2000.(Attachment #1). b)The number of license RC PO in Automation License Manager:( Attachment #2). c)The number of Archive tags and its limit is:1066 of Unlimited.( Attachment #3). d)The License Error:( Attachment #4). e)The Detail of Error:( Attachment #5). f)The window after press open Key:( Attachment #6). But my question is : why the License Error occurred , when no. of Archived Tags in Taglogging exceed from 512?!! While I have installed "WinCC User Archived" & " WinCC Arch(80000)" . Best regards SA_JOO Attachment21_08_2011.zip (160 Downloads) |
8/22/2011 11:45 PM | |
Posts: 2661 Rating: (279)
|
You do not have the proper WinCC Archive license... |
8/23/2011 6:54 AM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
HI ! Please let me to know the proper WinCC Archive license for this matter. best regards. SA_JOO |
8/28/2011 6:54 AM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
Hello to all special thanks for your support. Please answer my question. best regards SA_JOO |
8/29/2011 7:14 AM | |
Joined: 8/10/2011 Last visit: 5/5/2024 Posts: 15 Rating: (1) |
HI ! Please let me to know the proper WinCC Archive license for this matter. best regards. SA_JOO |
8/31/2011 7:03 PM | |
Posts: 2661 Rating: (279)
|
You need the WinCC Archive 1500 tag license [order number 6AV6371-1DQ17-0AX0]. See the Products contained drop down in the following link: Product: WinCC V7.0(6AV63.1-....7-0...) 512K tags license is built-in. |
9/3/2011 10:45 AM | |
Posts: 2661 Rating: (279)
|
80000are WinCC tags and 1500 Process Objects (PO's). From PCS7 V7.0 the WinCC (PCS7 OS)tags are counted as PO's and not tags. One PO equals 50 or 60 tags depending on the version. See the following FAQ: How are the licenses for the AS and OS counted as from PCS 7 V7.0? |
Follow us on