Joined: 4/24/2006 Last visit: 9/25/2024 Posts: 8742 Rating: (1168) |
Dear Shahiiee, In a Central rack, behind a CPU, you can use 8 signalmodules. Place 4 -11. When you want to use more modules, you can use an extension rack. By using IM365 or IM360 and IM361, they can be placed at place 3. When you have an IM153-4, there you can use 12 modules behind IM153-4. Edit: When you have IM153-4, you can not use Failsafe modules New ET200M PROFINET Interface Module with enhanced Functions released for delivery You can use IM153-2 (profibus) also possible to use 12 modules and Failsafe modules Hope this will help. Best regards, Wizard |
Last edited by: Wizard at: 7/22/2010 8:52 AMLast edited by: Wizard at: 7/22/2010 8:50 AMFailsafe and IM153-2 |
|