Well, I'm not that good expert to advise you 100% working solutions. But here it is, I've found information from PCS7 Compendium part A - Configuration:
I would reinstall Windows. Are you using SIMATIC IPC or usual PC? Cause IPC have Restore DVD – a good thing to reinstall whole system. I have several IPCs at the office for new project and at the first launch I should have entered PC name and I chose, for example, 00CWA91. But leading numbers should be avoided. So I renamed the stations to CWA91 etc. And I was working under my project having no access problems. However later I reinstalled Windows with Restore DVD just in case And check the user rights. Manual "PCS 7 - PC Configuration and Authorization", 4.4.7 Setting up user groups and users. Something remains in renamed PC's system... For example, the user group SQLServer2005MSSQLUser$<COMPUTERNAME>$WINCC containes the old PC name. Also I've got troubles when downloading project to OS Client (Windows XP) from ES Station (Windows Server). I should've been logged in as some new user (except Administrator) in OS and ES to be able to download a project. Do you think it's ok to have different versions of WinCC in one project? What version is installed on ES? I think that ES is creating OS projects for a specific version of WinCC that should not be open under other version. Am I wrong? |
4/26/2012 12:41 PM | |
Joined: 10/26/2011 Last visit: 9/9/2024 Posts: 762 Rating: (191) |
Hello I think, you have now PCS 7 V7.0 SP3... If that is right, you have to upgrade your older project(s) to the newer version. You cannot mix the versions. That will be the reasons of your error messages. Regards |
SIMATIC PCS 7 - Overview |
|
4/26/2012 12:55 PM | |
Joined: 10/26/2011 Last visit: 9/9/2024 Posts: 762 Rating: (191) |
Hello I am confused. In the top, you wrote, that your new PC has PCS 7 V7.0 SP3 "Exising OS PC are having PCS7 V7.0 SP1 & WinCC V6.2 SP2 on Windows XP SP2, New OS PC is having PCS7 V7.0 SP3 & WinCC V6.2 SP3+HF1on Windows XP SP3."
|
SIMATIC PCS 7 - Overview |
|
4/26/2012 9:19 PM | |
Joined: 11/4/2011 Last visit: 8/25/2024 Posts: 253 Rating: (53) |
Excuse me, but haven't you forgot to Assign OS Server to the Client? Here are the documents that mention about a procedure: 1. PCS 7 Compendium Part A - Configuration Guidelines => 7.1 Project settings => 7.1.1 Defining the server assignment 2. PCS 7 - Configuration Manual Operator Station => 16.1.2 How to Download Server Data |
This contribution was helpful to1 thankful Users |
4/29/2012 2:20 PM | |
Posts: 691 Rating: (37) |
Hello Saravana kumar Are you able to access the Server from your New OS Client PC. Make sure that NewOS PC must connect to the Server at the Startup , It should not ask any login while accessing the Server |
This contribution was helpful to1 thankful Users |
4/29/2012 4:18 PM | |
Joined: 11/4/2011 Last visit: 8/25/2024 Posts: 253 Rating: (53) |
Sorry, what path are you opening? You mean Windows shared folder? |