Hi everybody. I am doing a graduating project, where I simulate a scada system with step 7 and WinCC. So far I have a working project, with a mpi connection between step 7 and WinCC. When I try to make an alarm log, I get the message "No connection to data server". I have found this answer in FAQ, but don't know how tosolve it. How do you generate a server package? Where is WinCC information system? My WinCC version is 6.2. https://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=en&objid=16720071&caller=view QUESTION: ANSWER: Note: |
Last edited by: Arni S at: 11/17/2008 2:33 PMIt could not have been simpler. I forgot to add alarm runtime in computer properties startup |
|