6/14/2010 1:24 PM | |
Joined: 3/21/2006 Last visit: 9/10/2024 Posts: 10228 Rating: (1181) |
Hello, Look at SIMOREG DC Master 6RA70; software version 3.1 (on page 228th). In your case: P771 (B104) this is signal run. Source for output value at binary output 1. Selection of binector to be injected at binary selectable output, terminal 46. P772 (B106) this is for fault signal. Source for output value at binary output 1. Selection of binector to be injected at binary selectable output, terminal 48. Also is possible to put delays using P775 and to invert signal using P770.01. Best regards, Hristo Mihalev |
6/15/2010 8:01 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877) |
Hi Hristo, Thank you very much for your valuable information. With best regards, DEEP. |