Industry Online Support
Technical Forum
6/27/2008 5:31 PM | |
Posts: 2661 Rating: (279) |
Yes. Check the follwoing FAQ: How do you program the PROFIBUS DP diagnostics blocks FB125, FC125 for SIMATIC S7? What are the baud rates (on the 315and 400 sides)? |
6/30/2008 10:12 AM | |
Posts: 1776 Rating: (95)
|
Hi, have you also think about PCS 7 Asset Management A nice document can be found here http://support.automation.siemens.com/WW/view/en/27833758 Also interesting is the following http://support.automation.siemens.com/WW/view/en/10343086 but you need extra software |
7/1/2008 5:41 PM | |
Posts: 2661 Rating: (279) |
The main steps are as follows: 1. Download project and online help file from FAQ mentioned in my last post. 2. Retrieve project and install online help (by double clicking on .exe file). 3. Copy FB125 and FC125 from the blocks container of the project just retrieved to the blocks container of your project. 4. Open any CFC in your project. 5. From menu item Options/Block Types, import FB125 and FC125 from offline block folder to chart folder. 6. Drag and drop FB125 and FC125 from block catalog, DP folder in to your CFC and parameterize them. The online help describes the blocks in detail. Also pay attention to the notes in the following FAQ: Integrating STL programs in a CFC program |
7/2/2008 11:18 AM | |
Posts: 7 Rating: (0) |
Thanks very much for your assitance. |