Industry Online Support
Technical Forum
6/10/2010 9:34 AM | |
Posts: 2 Rating: (0) |
hi . why i can't configure DX ( direct data exchange) in my project while my project's master has DX capablity
Attachmentprofibus.zip (50 Downloads) |
6/10/2010 9:59 AM | |
Joined: 3/21/2006 Last visit: 9/10/2024 Posts: 10228 Rating: (1181)
|
Hello, Unfortunately your type of IM153-1 doesn't support DX. Look at Which SIMATIC S7 modules support the "Direct Data Exchange" function (internode communication)? Best regards, Hristo Mihalev |
Last edited by: UMENCHO at: 6/10/2010 11:53 AM;) |
|
6/10/2010 10:47 AM | |
Joined: 8/25/2006 Last visit: 9/24/2024 Posts: 2209 Rating: (278) |
Hello. Look at the newest IM153-1 with order number 6ES7153-1AA03-0XB0, which supports direct data exchange as sender. In your project you use 6ES7153-1AA00-0XB0. |
This contribution was helpful to2 thankful Users |