12/18/2008 5:01 PM | |
Joined: 7/2/2008 Last visit: 8/26/2024 Posts: 928 Rating: (308) |
Hello Simochan_sm, You have to make sure that OB83 exists on CPU program. You have to disable automatic switch over before removing or inserting module. This FAQ tells you how configure hot swapping feature in software redundancy. Best regards. |
12/19/2008 2:13 AM | |
Posts: 6 Rating: (0) |
Dear H-H, Thank you for your reply. I have already download O83. But the problem still occur. |
12/21/2008 9:22 AM | |
Joined: 7/2/2008 Last visit: 8/26/2024 Posts: 928 Rating: (308) |
Please check the operating parameters of the DP slave. |