7/28/2009 7:43 PM | |
Posts: 2661 Rating: (279) |
In CFC editor Options -> Customize -> Compile/Downloadadjust "Installed blocks per runtime group or OB" to 200 (for example). See attachment. Are you sure?First change the priority to 16 and only then enter 35. Regards AttachmentOB with special handling.pdf (316 Downloads) |
This contribution was helpful to1 thankful Users |