12/2/2014 6:08 PM | |
Joined: 1/28/2009 Last visit: 9/10/2024 Posts: 6849 Rating: (1365)
|
Hello C.kt, If you use S7-F/FH Systems It is not possible in SCL, you can only use CFC to call blocks from fail-safe library.You need to search the options in CFC like creating F-Block types.Check section 5.7 of the following manual:
SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming I hope this helps, Hamid Hosseini |
Last edited by: hdhosseini at: 12/2/2014 6:15 PM |
|
This contribution was helpful to1 thankful Users |