Hello. So, you have 850A armature/30A field drive and want to run 60A armature/2.8A field motor. Refer to chapter 6.6 of themanualabout load and shunt resistors for armature/field curcuits, which may be removed for reducing rated converter armature/field currents. Also don't forget to reduce this currents in parameters P072, P073, as described in chapter 7.5.
|