Hello. May be you have an old list manual, try to look in thelatestversion: 9: Reference speed (p2000) not set (factory setting value must be modified)!
|
7/21/2014 8:03 AM | |
Posts: 70 Rating: (0) |
Hallo too KSN, Ok thanks no.9 fault has now gone, but the fault appears no.8 must be filled with any value, Field characteristic (p50120 ... p50139)? Thanks. |
7/21/2014 8:06 AM | |
Posts: 70 Rating: (0) |
Here I DC motors without field, because it already has a permanent magnet motors. |
7/21/2014 8:18 AM | |
Joined: 8/25/2006 Last visit: 9/23/2024 Posts: 2209 Rating: (278) |
Hello. If your motor with permanent magnet, disable field in p50082=0 and field weakening in p50081=0.
|
7/21/2014 9:00 AM | |
Posts: 70 Rating: (0) |
Previously, already set to 0 P50082 and P50081 |