Hello, The attached snap shot SLM manufacturing month & year is Aug - 2012. Since it is in storage for more than 3-4 years, user need to re-form capacitors. Please refer attached sheet for capacitor re-formation. (Extracted from Siemens Sinamics manual) HTH AttachmentSinamics infeed mm capacitor reforming procedure.pdf (114 Downloads) |