Hello, maybe this will be helpful to you: Cyclic script activated by trigger. Can i do that?I always use a toggle bit (live bit) to check if connection to HMI is ok. It toggles with 500 ms. If either ON-time or OFF.time exceeds 500 ms, then communication is broken.If you have something similar, you could trigger your script on "value change of that bit AND popoup window is open".regards |