7/11/2014 1:19 PM | |
Posts: 12 Rating: (1) |
Thanks for your tip Bizur We have an ES with with WinCC7.0 RC 64k license and 2 standalone OS with WinCC 7.0 RT license. WinCC-comfiguration is an upgradet version, and now integrated with a Step7-Multiproject from an older ES with some PCS7 software. OS are asking for PO-license! The "Save As(with reorganisation Slow) option generated three error message related to missing PO-licenses, so the "Save As"-option vas aborted. Since reorganization was an issue, I triedReorganization function in Simatic Manager: 1. Close projects and exit in WinCC Explorer 2. Close open projects in Simatic Manager, 3. Simatic Manager: File-->Reorganize-->select project"XX"-->OK Now WinCC Explorer shows correct license information. See attached pdf-file Thanks again for the reorganization idea Tore
AttachmentWinCC asking for PO-license.pdf (597 Downloads) |
This contribution was helpful to1 thankful Users |