1/16/2020 8:40 AM | |
Joined: 4/6/2019 Last visit: 2/17/2024 Posts: 53 Rating: (0) |
hi everybody who has this error on the pcx ? Error 7194: The automation station could not be connected online! whats is the best way to PCX reset factory? Best Regards ------------------------------------------------------------------------------------------ |
Last edited by: The Helping Hand at: 01/17/2020 13:40:15New subject after splitting |
|
1/16/2020 3:17 PM | |
Joined: 11/8/2017 Last visit: 9/19/2024 Posts: 337 Rating: (189) |
Hi, I've attached files from the FW Download Tool. These show the buttons to press to factory-reset a PX controller. Press and hold the Firmware button. Momentarily press the Reset button (whilst still holding the firmware button). Keep holding the Firmware button until the red Fault LED comes on - then release the Firmware button. Give it a minute or two, then it should be ready for a node-setup. Regards, AttachmentReset.zip (550 Downloads) |
1/17/2020 6:36 AM | |
Joined: 4/6/2019 Last visit: 2/17/2024 Posts: 53 Rating: (0) |
hi thank you ? it s need a pw for download , i cant download it best regards |
1/17/2020 12:56 PM | |
Joined: 11/8/2017 Last visit: 9/19/2024 Posts: 337 Rating: (189) |
Hi, I've never been asked for a password to download firmware into a PX. Can you attach a screen shot please? Regards, |
1/21/2020 6:54 PM | |
Joined: 4/6/2019 Last visit: 2/17/2024 Posts: 53 Rating: (0) |
hi thank your my friend I downloaded it , It can be downloaded now |
Follow us on