Hello, Today I did the Topology. Online I found the line between I/O module_2 to the XC208 red. Also from the diagnostics the switch was shown as Not reachable. Further, it was found o the diagnostics that the Profinet name and the assigned name of the switch were different. Updated the name and the error is cleared. Thank you for your guidance |