If you open WinCC Explorer on the ES, check that the ComputerName of the server IS the PC Name of your ES. |
Last edited by: SteBo at: 02/11/2021 09:20:09B r g d s , |
|
| 2/12/2021 8:02 AM | |
|
Joined: 10/3/2010 Last visit: 1/14/2026 Posts: 1572 Rating:
|
I have ES in Simatic Manager, not in PCS7 but I guess it should be similar. In WinCC Explorer the computer name should be the name of your ES computer. If you have a setting in PCS7 where you configure your server properties (please check attachment), make sure to uncheck "Computer name identical to PC station name" and leave "Computer name:" empty. If so, performing a download to the server station should change the computer name automatically indeed, if your ES is configured correctly. I assume that working with an ES in PCS7 is quite similar to working with an ES in Simatic Manager. If you want to be sure, you could try it on a non-critical moment (with a backup to rollback). |