(0)| 2/3/2011 3:59 PM | |
|
Posts: 799 Rating:
|
Dear richardstarr, never heard of this behaviour before. Are there any error or fault entries in the logfiles? regards |
| 2/10/2011 7:31 PM | |
|
Posts: 10 Rating:
|
Hi, Which logs should I be looking at? Sorry am not too experienced in these matters; any help would be really useful! Regards Richard
|
| 6/17/2011 9:29 PM | |
|
Posts: 7 Rating:
|
Hello, |
| 2/6/2015 12:56 PM | |
|
Posts: 7298 Rating:
|
Hello Koen, the ControlHost.exe is a process of WebNavigator-Server, you should have 5 instances of it. To find out, what the reason for the crash is, you should install AdPlus on the PC and configure it for watching the process "ControlHost.exe". If you have got a dump then, you can create a Support Request and send it to the Technical Support. How to use AdPlus is described here: https://support.industry.siemens.com/cs/#document/45020870?lc=en-WW Regards Georg Berghif |