Dear friends, Is there anyway totheSINAMICSG120inverteroverload andovercurrentdetectandautomaticallycutpower to themotor? Best regards Daniel Correia I want make the circuit in attachment but with Sinamics G120 inverter Attachmentpcse2.pdf (392 Downloads) |
| 1/16/2012 4:14 PM | |
|
Posts: 739 Rating:
|
Hi, the inverter protects it self, you only need a fuse for cable protection on inverter input. A Fuse between inverter and motor is not needed. The Cu2xx x includes motor protection by software and by PTC / KTY. To parametric it pls see Manuals http://support.automation.siemens.com/WW/view/en/30563628/133300 |
| 11/16/2014 4:31 PM | |
|
Posts: 3 Rating:
|
Motor overload at 160% for 60 seconds Motor overcurrent at 225% of VSD full load Is it possible in Sinamics G120 PM240+CU230P
|