6/7/2011 10:08 PM | |
Joined: 1/28/2009 Last visit: 9/10/2024 Posts: 6849 Rating: (1365) |
Please check the following Software (Desklock) which is a powerful software to just provide limited and authenticated permission to Windows' combination keys and all possible administrators' duties are controlled by a password and also you can also define start up programs. It worths testing. regards |
6/9/2011 8:19 AM | |
Joined: 10/3/2010 Last visit: 9/20/2024 Posts: 1562 Rating: (191) |
entry 44027453: How can you lock key combinations in WinCC V7.0 SP2 with Windows 7 or Windows Server 2008? http://support.automation.siemens.com/WW/view/en/44027453 |
B r g d s , |
|
9/10/2012 3:17 PM | |
Posts: 1776 Rating: (95)
|
Hi, see the link SteBo published |
4/23/2013 2:47 PM | |
Posts: 767 Rating: (69) |
Hello, I'm also looking for an option to enable key combinations during runtime. Normally the key combinations have to be disabled. I want toenablethemto help the engineers during service. With windows XP and 2003 the following solution works: http://support.automation.siemens.com/WW/view/en/22326550 But this doesn't work with windows 7 . Is there anyone who has an solution for Windows 7???? Thanks in advance! Cedric |
4/24/2013 10:59 AM | |
Joined: 1/17/2006 Last visit: 7/19/2024 Posts: 800 Rating: (63) |
Hi Experts, I also tried the solution SteBo provided: http://support.automation.siemens.com/WW/view/en/22326550 It should work with Win7 but itdoesn't. I tried to debug but it seems to work fine,but nolock or unlocking of the taskbar. Hope you can help out Jaap I used this script, it triggers fine and state switches from enable to disable but whithout any result. maybe it's an security setting in Windows?: #pragma code ("UseAdmin.DLL") #include "pwrt_api.h" #pragma code() #pragma code ("ALMXGINA.DLL") BOOL SetXGinaValue(unsigned int uiKey, BOOL *pbEnable, DWORD dwSize); #pragma code() BOOL bEnable; BOOL bOK; #define XGINA_ALLOW_SHUTDOWN 1 #define XGINA_ALLOW_LOGOUT 2 #define XGINA_ALLOW_CTL_ALT_DEL 3 #define XGINA_ALLOW_CTL_ESC 4 #define XGINA_ALLOW_ALT_ESC 5 #define XGINA_ALLOW_ALT_TAB 6 bEnable = PWRTCheckPermission(1, TRUE); bOK = SetXGinaValue(XGINA_ALLOW_SHUTDOWN , &bEnable , sizeof(bEnable )); bOK = SetXGinaValue(XGINA_ALLOW_LOGOUT , &bEnable , sizeof(bEnable )); bOK = SetXGinaValue(XGINA_ALLOW_CTL_ALT_DEL , &bEnable , sizeof(bEnable )); bOK = SetXGinaValue(XGINA_ALLOW_CTL_ESC , &bEnable , sizeof(bEnable )); bOK = SetXGinaValue(XGINA_ALLOW_ALT_ESC , &bEnable , sizeof(bEnable )); bOK = SetXGinaValue(XGINA_ALLOW_ALT_TAB , &bEnable , sizeof(bEnable )); printf("#I101: SetXGinaValue() - bEnable=%d bOK=%d (lock/unlock windows keys)\r\n", bEnable, bOK); |
5/30/2013 9:15 AM | |
Posts: 12 Rating: (0) |
Hi Cedric. We are using WinCC 7.0 SP3 +Update1. In my case the behaviour is constant: one computer is working all time, the others no. Regards
|
5/30/2013 11:29 AM | |
Joined: 3/21/2013 Last visit: 7/9/2013 Posts: 5 Rating: (0) |
Did you check firewall and virusscanning? It could be that something is blocked. I had that behavior whtihin V6SP4 and WinXP . Good luck. it's me "Jaapie" not AutoGen_469046 |
Last edited by: AutoGen_469046 at: 5/30/2013 11:37 AM |
|
5/30/2013 1:12 PM | |
Posts: 12 Rating: (0) |
Hi. The firewall is off and no antivirus is installed, as the computers are in a private VPN with no web acces. Ioan
|
Last edited by: Ioan at: 5/30/2013 1:13 PM |
|
9/10/2014 5:25 PM | |
Posts: 32 Rating: (1) |
Hello Molthoff Found the solution after a long time. I was also facing the same problem then started searching in internet but no good answer. Then tried by myself In Windows 7 : Open Registry Editor and go to the following path HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Siemens\WinCC\Winlogon\Permissions You can see all the blocked key combinations. All the values are Zero, that's why they are disabled. Make the values for each combination to One (1) to make then enabled. I hope this will help you. Thanks |
This contribution was helpful to1 thankful Users |